Drawn from the 112S1P configuration in the build sheet
This manufacturer has not uploaded photographs of this unit yet. What you see is drawn from its own build sheet. Ask them for site photographs before you order — and if you are the manufacturer, upload them from the portal.
HV String 358-280
358.4 V · 280 Ah · floor cabinet
- 90.32 kWh usable at 90% depth of discharge
- CATL LF280 cells, Grade A, 112S1P
- In-house BMS 3-tier BMU/BCU · CAN, MODBUS_TCP
- 6,000 cycles at 80% DoD · 5-year warranty
A 112S high-voltage string on 280 Ah cells, sized to replace a VRLA bank in an existing UPS room without touching the UPS.
5 years against manufacturing defect, and against usable capacity falling below 80% of rated within 6,000 cycles at 80% depth of discharge.
- Dispatch
- 45–60 days of a confirmed order
- Minimum order
- 1 unit
- Sold by
- Girnar Power
No payment is taken on this site. You get a proforma and Girnar Power's contact details; they confirm the order and raise the GST invoice.
Payment terms
40% advance against proforma, 60% before dispatch, by NEFT or RTGS.
Technical specification
Electrical
| Nominal voltage | 358.4 V |
|---|---|
| Configuration | 112S1P |
| Nominal energy | 100.35 kWh |
| Usable energy | 90.32 kWh at 90% depth of discharge |
| Continuous discharge | 100 kW · 279 A |
| Maximum charge | 50 kW |
Cells and BMS
| Chemistry | LFP |
|---|---|
| Cell make | CATL LF280 |
| Cell grade | Grade A |
| Cell capacity | 280 Ah |
| BMS make | In-house 3-tier BMU/BCU |
| BMS comms | CAN, MODBUS_TCP |
Mechanical and environmental
| Enclosure | cabinet |
|---|---|
| Ingress rating | IP54 |
| Cooling | forced air |
| Dimensions | 1100 × 900 × 2100 mm |
| Weight | 900 kg net · 975 kg gross |
Life, warranty and compliance
| Cycle life | 6,000 cycles at 80% DoD |
|---|---|
| Warranty | 5 years |
| Certifications on file | UN 38.3 |
| HSN code | 8507 |
| GST | 18% |
| Country of origin | India (assembled) · cells imported |
| Dangerous goods | UN3480 · Class 9 · 1,00,350 Wh — surface freight only |
Build sheet
What is actually inside the box, with the document that backs each claim. If a competing listing will not publish theirs, that is the comparison.
Warranty and terms
Set by Girnar Power, who warrants this pack and raises the invoice.
5 years against manufacturing defect, and against usable capacity falling below 80% of rated within 6,000 cycles at 80% depth of discharge.
- · Installation outside the rack specification
- · Operation outside the stated float and cycling window
- · Any modification to the BMS or its firmware
- Minimum order
- 1
- Lead time
- 45–60 days
40% advance against proforma, 60% before dispatch, by NEFT or RTGS.
Built to order against a confirmed UPS model. Not returnable once manufacturing starts.
- · Site readiness — floor loading, ventilation and DC run — is the customer's scope.
- · UPS compatibility confirmed against the model number before the order is accepted.
- · Freight quoted per consignment; this cabinet is a part-load booking.
Order from Girnar Power
Send the order request and you get a proforma and Girnar Power's direct phone, email and WhatsApp. They confirm, arrange freight and raise the GST invoice. No payment is taken on this site.